1600 DIST.PROT. FAULT DETECTION
1602 Ie> Earth fault detection Ie>
min. 0.10 I/In
max. 1.00 ©©©©
1603 Ie>> Earth flt. detect. (independent of 1707) Ie>>
min. 0.10 I/In
max. 4.00 ©©©©
1610 Iph>> Overcurrent detection Iph>>
min. 0.25 I/In
max. 4.00 ©©©©
1611 Iph> Minimum current for fault detection Iph>
min. 0.10 I/In
max. 1.00 ©©©©
1612 Uphe(I>>) Undervoltage pick-up at I>> (phase-earth)
min. 20 V
max. 70 ©©©©
1613 Uphe(I>) Undervoltage pick-up at I> (phase-earth)
min. 20 V
max. 70 ©©©©
1614 Uphph(I>>) Undervoltage pick-up at I>> (phase-phase)
min. 40 V
max. 130 ©©©©
1615 Uphph(I>) Undervoltage pick-up at I> (phase-phase)
min. 40 V
max. 130 ©©©©
1616 Iphi> Overcurrent fault detection (phi) Iphi>
min. 0.10 I/In
max. 2.00 ©©©©
1617 Uphe(Iphi>) Undervoltage pick-up at Iphi> (phase-earth)
min. 20 V
max. 70 ©©©©
1618 Uphp(Iphi>) Undervoltage pick-up at Iphi> (phase-phase)
min. 40 V
max. 130 ©©©©
1619 phi> U/I/phi-fault detection phi>
min. 30 Ý
max. 60 ©©©©
1620 phi< U/I/phi-fault detection phi<
min. 90 Ý
max. 120 ©©©©
1621 Iph> Minimum current for fault detection Iph>
min. 0.10 I/In
max. 4.00 ©©©©
1622 X+A Fault detection forward reach X+A
min. 0.10 Ï
max. 250.00 ©©©©