$SSHQGL[6$
9

&*&
1802 Ue> Displacement voltage for earth fault det. Ue>
min. 10 V
max. 100 ©©©©
1803 PHASE PREF Phase preference for double earth faults
L3(L1) ACYCLIC [ ] L3(L1) acyclic
L1(L3) ACYCLIC [ ] L1(L3) acyclic
L2(L1) ACYCLIC [ ] L2(L1) acyclic
L1(L2) ACYCLIC [ ] L1(L2) acyclic
L3(L2) ACYCLIC [ ] L3(L2) acyclic
L2(L3) ACYCLIC [ ] L2(L3) acyclic
L3(L1) CYCLIC [ ] L3(L1) cyclic
L1(L3) CYCLIC [ ] L1(L3) cyclic
ALL [ ] All
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
2000 POWER SWING
2002 P/S PROGR. Program of power swing (P/S) function
BLOCK ALL [ ] Block all zones
BLOCK Z1 ONLY [ ] Block Z1 only
BLOCK ALL BUT Z1 [ ] Block all but Z1
BLOCK Z1-Z2 [ ] Block Z1-Z2
2006 P/S Trip Power swing trip
NO []no
YES [ ] yes
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
2100 TELEPROTEC PERM. UNDERREACH
2101 PUTT Permissive underreach transfer trip
ON []on
OFF [ ] off
2102 PUTT MODE Permissive underreach transfer trip mode
Z1B ACCELERATION [ ] Z1B acceleration
FD ACCELERATION [ ] FD acceleration
2103 T-SEND-PRL Send signal prolongation for PUTT
min. 0.01 s
max. 32.00 ©©©©
2104 T-REC-PROL Receive signal prolongation for PUTT
min. 0.00 s
max. 32.00 ©©©©
2106 T-SEND-DEL Send signal delay for PUTT
min. 0.00 s
max. 32.00 ©©©©
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
2200 TELEPROTEC PERM. OVERREACH
2201 POTT Permissive overreach transfer trip
ON []on
OFF [ ] off