2202 POTT MODE Permissive overreach transfer trip mode
Z1B RELEASE [ ] Z1B release
FD DIREC RELEASE [ ] Direct. comparison
Z1B UNBLOCK [ ] Unblocking with Z1B
FD UNBLOCK [ ] Unblocking with FD
Z1B BLOCKING [ ] Blocking with Z1B
PILOT WIRE COMP. [ ] Comp. via pilot wire
REVERS INTERLOCK [ ] Reverse interlocking
2203 T-TRANSBLO Transient blocking time after external fault
min. 0.01 s
max. 32.00 ©©©©
2204 T-WAIT Waiting time for trans.block. (missing recept)
min. 0.01 s
max. 32.00/Ñ ©©©©
2206 T-SEND-PRL Send signal prolongation for POTT
min. 0.01 s
max. 32.00 ©©©©
2210 POTT DirFD Effect. direction for directional comparison
FORWARDS [ ] Forwards
REVERSE [ ] Reverse
NON-DIRECTIONAL [ ] Non-directional
2211 TW REVERSE Waiting time for trans.block. (reverse faults)
min. 0.01 s
max. 32.00/Ñ ©©©©
2212 T-SEND DEL Send signal delay for POTT
min. 0.00 s
max. 32.00 ©©©©
2220 ECHO Echo function for weak infeed
ON []on
OFF [ ] off
2221 T-ECHO-DEL Echo delay time
min. 0.01 s
max. 32.00/Ñ ©©©©
2222 T-ECHO-IMP Duration of echo impulse
min. 0.02 s
max. 32.00 ©©©©
2223 T-ECHO-BLO Echo blocking time
min. 0.01 s
max. 32.00 ©©©©
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
2300 USER LOGIC FUNCTIONS
2302 T-PICKUP 1 1st user logic function: Pick-up time
min. 0.00 s
max. 32.00/Ñ ©©©©
2303 T-DROP 1 1st user logic function: Drop-off time
min. 0.00 s
max. 32.00/Ñ ©©©©