$SSHQGL[6$
9
&* &
2611 CHARACT.PH Emerg. phase overcurrent characteristic
DEFINITE TIME [ ] Definite time
NORMAL INVERSE [ ] Normal inverse
VERY INVERSE [ ] Very inverse
EXTREMELY INVERS [ ] Extremely inverse
2612 I> Phase overcurrent threshold (DT) I>
min. 0.10 I/In
max. 4.00 I/In
max. 15.00 ©©©©
2613 T-I> Delay time for I> TI>
min. 0.00 s
max. 32.00/Ñ ©©©©
2614 Ip Phase o/c threshold (inverse time IDMT) Ip
min. 0.10 I/In
max. 4.00 ©©©©
2615 T-Ip Time multiplier for Ip (inverse time IDMT) Tp
min. 0.05 s
max. 32.00/Ñ ©©©©
2616 MEA.FORM.P Phase current measurement format
WITHOUT HARMON. [ ] Without harmonics
WITH HARMONICS [ ] With harmonics
2621 M/CLOSE PH Phase overcurrent stage effect.: Manual close
I>> UNDELAYED [ ] I>> undelayed
I>/Ip UNDELAYED [ ] I>/Ip undelayed
INEFFECTIVE [ ] Ineffective
2623 RAR ZONE P Phase overcurrent stage effect.: Auto reclose
I>> WITH AR [ ] I>> only with AR
I>> ALWAYS [ ] I>> always
2631 EMER.O/C E State of emergency overcurrent prot.: earth
ON []on
OFF [ ] off
2632 IE>> Highset earth overcurrent threshold (DT) IE>>
min. 0.10 I/In
max. 4.00 ©©©©
2633 T-IE>> Delay time for IE>> TIE>>
min. 0.00 s
max. 32.00/Ñ ©©©©
2641 CHARACT. E Emergency earth overcurrent characteristic
DEFINITE TIME [ ] Definite time
NORMAL INVERSE [ ] Normal inverse
VERY INVERSE [ ] Very inverse
EXTREMELY INVERS [ ] Extremely inverse
2642 IE> Earth overcurrent threshold (DT) IE>
min. 0.10 I/In
max. 4.00 ©©©©
2643 T-IE> Delay time for IE> TIE>
min. 0.00 s
max. 32.00/Ñ ©©©©
©©©©©