$SSHQGL[6$
9
&*&
2644 IEp Earth o/c threshold (inverse time IDMT) IEp
min. 0.10 I/In
max. 4.00 ©©©©
2645 T-IEp Time multiplier for IEp (inv. time IDMT) TEp
min. 0.05 s
max. 32.00/Ñ ©©©©
2646 MEA.FORM.E Earth current measurement format
WITHOUT HARMON. [ ] Without harmonics
WITH HARMONICS [ ] With harmonics
2651 M/CLOSE E Earth overcurrent stage effect: Manual close
IE>> UNDELAYED [ ] IE>> undelayed
IE>/IEp UNDELAY. [ ] IE>/IEp undelayed
INEFFECTIVE [ ] Ineffective
2653 RAR ZONE E Earth overcurrent stage effect: Auto reclose
IE>> WITH RAR [ ] Ie>> with RAR
IE>> ALWAYS [ ] Ie>> always
2680 CHARACTERISTIC 1 Characteristic curve 1
2681 CHARACTERISTIC 2 Characteristic curve 2
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
2900 MEAS.VALUE SUPERVISION
2901 SYM.Uthres Symmetry threshold for voltage monitoring
min. 10 V
max. 100 ©©©©
2902 SYM.Fact.U Symmetry factor for voltage monitoring
min. 0.58
max. 0.95 ©©©©
2903 SYM.Ithres Symmetry threshold for current monitoring
min. 0.10 I/In
max. 1.00 ©©©©
2904 SYM.Fact.I Symmetry factor for current monitoring
min. 0.10
max. 0.95 ©©©©
2905 SUM.Ithres Summation threshold for current monitoring
min. 0.05 I/In
max. 2.00 ©©©©
2906 SUM.Fact.I Factor for current summation monitoring
min. 0.00
max. 0.95 ©©©©
2907 UMEAS U< Threshold for voltage failure monitor
min. 10 V
max. 125 ©©©©
2908 UMEAS I> Minimum current for voltage failure monitor
min. 0.06 I/In
max. 1.00 ©©©©