7SG11 Argus 8 Appendix
©2011 Siemens Protection Devices Limited Chapter 9 Page 4 of 13
VOLTAGE MENU (can be used also for SYSTEM A and SYSTEM B MENUS)
SETTING RANGE SET VALUE
Gn V Element 1 Delay 0.00 – 20.00 step 0.01 sec
20.0 – 100.0 step 0.5 sec
100 – 600 step 1.0 sec
Gn V Element 1 Hysteresis 1% – 90% step 1%
Gn V Element 1 O/P Phases Any 1, All
Gn V Element 2 Operation OFF, O/V, U/V
Gn V Element 2 Setting OFF, 5V – 200V step 0.5V
Gn V Element 2 Delay As Element 1 Delay
Gn V Element 2 Hysteresis 1% – 90% step 1%
Gn V Element 2 O/P Phases Any 1, All
Gn V Element 3 Operation OFF, O/V, U/V
Gn V Element 3 Setting OFF, 5V – 200V step 0.5V
Gn V Element 3 Delay As Element 1 Delay
Gn V Element 3 Hysteresis 1% – 90% step 1%
Gn V Element 3 O/P Phases Any 1, All
Gn V Element 4 Operation OFF, O/V, U/V
Gn V Element 4 Setting OFF, 5V – 200V step 0.5V
Gn V Element 4 Delay As Element 1 Delay
Gn V Element 4 Hysteresis 1% – 90% step 1%
Gn V Element 4 O/P Phases Any 1, All
NEUTRAL VOLTAGE MENU
SETTING RANGE SET VALUE
Gn 3Vo Element 1 Setting 0FF, 1 – 100V step 0.5V
Gn 3Vo Element 1 Delay 0.00 – 20.00 step 0.01 sec
20.0 – 100.0 step 0.5 sec
100 – 600 step 1.0 sec
Gn 3Vo Element 2 Setting 0FF, 1 – 100V step 0.5V
Gn 3Vo Element 2 Delay As Element 1 Delay
NPS OVERVOLTAGE MENU
SETTING RANGE SET VALUE
Gn V2 Element 1 Setting 0FF, 1 – 100V step 0.5V
Gn V2 Element 1 Delay 0.00 – 20.00 step 0.01 sec
20.0 – 100.0 step 0.5 sec
100 – 600 step 1.0 sec
Gn V2 Element 2 Setting 0FF, 1 – 100V step 0.5V
Gn V2 Element 2 Delay As Element 1 Delay