EasyManua.ls Logo

Siemens AC-21 - Page 2

Siemens AC-21
50 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Siemens LV 10 · 2004
7/2
Switch Disconnectors and Fuses
Introduction
7
Overview
Type 3LD20 3LD21 3LD22 3LD25 3LD27 3LD28
SENTRIC LD main control and EMERGENCY-STOP switches from 16 A to 125 A
Rated uninterrupted current
I
U
at 35 °C ambient temperature
A 16 25 32 63 100 125
Rated operating voltage
U
e
V 690 690 690 690 690 690
AC-3 motor load switch
operational switching of individual motors
at 220 ... 240 V kW 3.0 4.0 5.5 11.0 18.5 22.0
at 380 ... 440 V kW 5.5 7.5 9.5 18.5 30.0 37.0
at 660/690 V kW 5.5 7.5 9.5 15.0 22.0 30.0
AC-23A main control switch,
maintenance switch
Frequent, but not operational switching of
individual motors
at 220 ... 240 V kW 4.0 5.0 6.0 11.0 18.5 22.0
at 380 ... 440 V kW 7.5 9.5 11.5 22.0 37.0 45.0
at 660/690 V kW 7.5 9.5 11.5 18.5 30.0 37.0
Switch versions
Front mounting
•Central
Four-hole ✓✓
Base mounting
•Central
Four-hole ✓✓
Distribution board mounting ✓✓
Molded-plastic enclosure
Heavy-gauge threaded joints ✓✓
Metric screws
Switch accessories
4th pole (N conductor)
(leading switch-on,
delayed switch-off contact)
✓✓
N terminal
PE/ground terminal ✓✓
Auxiliary contacts
1 NO + 1 NC
1 NO ✓✓
1 NC

Related product manuals