Siemens Acvatix SAX61 MO Series - Signal and Characteristic Configuration

Siemens Acvatix SAX61 MO Series
87 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
56 / 87
Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en
Smart Infrastructure Functions and control 2020-01-30
4.4 Positioning signal and flow characteristic
selection
1)
Factory setting: All DIL switches set to OFF Ω
Actuator Valve VVF.. / VVG41.. Totally
log
lin
Actuator Combi-Valve VPF43/VPF53 Totally
log
lin
Y, Z Positioning signal
H Stroke
V Volumetric flow
Acting direction: Direct
Acting direction: Reverse
SAX61.03/MO: Positioning signal and flow characteristic selection are not
permissible
Positioning signal "Y"
Position
feedback "U"
Flow characteristic
OFF
1)
DC 0…10 V DC 0…10 V
log =
equal-
percentage
ON DC 4…20 mA DC 0…10 V
lin =
linear
DIL switches
Flow characteristic
SAX61.03 / SAV61.00
with VVF..
Flow characteristic
SAY61P03 / SAX61P03 /
SAV61P00 with VPF..
Note