EasyManua.ls Logo

Siemens Acvatix SAX61 MO Series - Page 65

Siemens Acvatix SAX61 MO Series
87 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
65 / 87
Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en
Smart Infrastructure Functions and control 2020-01-30
Parameters
259 Op mode R 1 = POS
-
260 MinPosition R 0…100% = 0…10000 0%
261 MaxPosition R 0…100% = 0…10000 100%
262 Actuator runtime R 30s 30s
263 Positioning signal
characteristic
between Y and U
R 0 = Linear (e.g. SAX61../MO + V_G41)
1 = Logarithmic (e.g. SAS61../MO + V_G44)
-
264 Tolerance blockade
monitoring
R 0…100% = 0…10000 4%
513 Backup mode RW 0 = Move to backup position
1 = Maintain last position / 2 = Disabled
2 = Disabled
514 Backup position RW 0…100% = 0…10000 0%
515 Backup timeout RW 60…900s 900s
516 Startup setpoint RW 0…100% = 0…10000 0%
764 Modbus address RW 1…248 / 255 = “unassigned” 255 = “unassigned”
765 Baud rate RW 0 = auto / 1 = 9600 / 2 = 19200 / 3 = 38400 /
4 = 57600 / 5 = 76800 / 6 = 115200
0
766 Transmission
format
RW 0 = 1-8-E-1 / 1 = 1-8-O-1 / 2 = 1-8-N-1 / 3 = 1-8-N-2 0
767 Bus termination RW 0 = Off / 1 = On
120 Ω electronically switchable
0
768 Bus config.
command
RW 0 = Ready / 1 = Load / 2 = Reject 0
769 Status R See “Function description”, section, “Register
769 “Status”“, page 68
-
Reg. Name R/W Value Example
Device information
1281 Factory Index R Two bytes, each coding
an ASCII char.
5A 00 à “Z” 00
Device is of Series “Z”
1282 Factory Date HWord R Two bytes, the lower
coding the Year (hex)
Read 1282 à 000F
Read 1283 à 0418
HWord LWord
-- YY MM DD
Hex 00 0F 04 18
Dec 00 15 04 24
à Device was manufactured
24 April, 2015
1283 Factory Date LWord R High byte: coding the
month (hex)
Low byte: coding the day
(hex)
1284 Factory SeqNo HWord R Hword + LWord = HEX-
representation of
Sequence number:
Read 1284 à 000A
Read 1285 à A206
AA206(hex) à 696838 (dec)
à Device has sequence
number 696838
1285 Factory SeqNo LWord R
1409 ASN [Char_16..15] R Each register: Two bytes,
each coding an ASCII
char.
ASN is coded beginning
with reg. 1409
Example:
0x47 44 = GD
0x42 31 = B1
0x38 31 = 81
0x2E 31 = .1
0x45 2F = E/
0x4D 4F= MO
à ASN is GDB181.1E/MO
1410
ASN [Char_14..13]
R
1411
ASN [Char_12..11]
R
1412
ASN [Char_10..9]
R
1413 ASN [Char_8..7] R
1414
ASN [Char_6..5]
R
1415 ASN [Char_4..3] R
Reserve
1416 ASN [Char_2..1] R

Table of Contents