75 / 87
Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en
Smart Infrastructure Technical data 2020-01-30
SAY.. SAX.. SAV.. SAL..
Environ-
mental
conditions
Operation IEC 60721-3-3
Climatic conditions Class 3K5
Mounting location Indoors (weather-protected)
6)
Temperature General -15…55 °C
Humidity
(noncondensing)
5…95 % r.h.
Transport IEC 60721-3-2
Climatic conditions Class 2K3
Temperature -2570 °C
Humidity <95 % r.h.
Storage IEC 60721-3-1
Climatic conditions Class 1K3
Temperature -1555 °C
Humidity 5…95 % r.h.
Max. media temperatur when mounted
on valve
130 °C 130 °C 130 °C
7)
120 °C
SAY.. SAX.. SAV.. SAL..
Directives
and
Standards
Product standard EN60730-x
Electromagnetic compatibility
(Application)
For residential, commercial and industrial environments
EU Conformity (CE) A5W00000333
8)
CE1T4501x1
8)
CE1T4503xx
8)
CE1T4502X1
8)
RCM Conformity AC 230 V A5W00000334
8)
CE1T4515X4
8)
CM1T4503_C1
8)
-
EAC Conformity Eurasia conformity for all SA..-variants
UL, cUL AC 230 V -
AC/DC 24 V UL 873 http://ul.com/database; File number E35198
Environ-
mental
compati-
bility
The product environmental declarations contain data on environmentally
compatible product designs and assessments (RoHS compliance, materials
composition, packaging, environmental benefit, disposal):
7173310559Ben
7)
7173310559Ben
7)
A6V101083254
7)
7173310522A
7)
CE1E4502en
7)
Dimensions
See "Dimensions" (page 80)
Weight Excl. packaging
See "Dimensions" (page 80)
Accessories Potentiometer ASZ7.5
9)
0…1000 Ω ± 5%
Voltage DC 10 V (SELV)
Current rating < 4 mA
Auxiliary switch ASC10.51
9)
Switching capacity
External supply line protection
US installation, UL & cUL
AC 24…230 V, 6 (2) A, floating
See section power supply
AC 24 V class 2, 5 A general purpose
Stem heating element ASZ6.6
Power supply
AC / DC 24 V ± 20 %
Power consumption
at 50 Hz
50 VA / 30 W
Inrush current (cold) Max. 8.5 A (max. Temperatur 85 °C / 185 F)
Function module AZX61.1 for SA..61..
9)
Switching capacity AC 24…230 V, 6 (2) A, floating
External supply line protection See section power supply
US installation, UL & cUL AC 24 V class 2, 5 A general purpose
1)
Switching time for RMS of the sine wave at nominal voltage
2)
SAL.T20 / T40 have a minimum holding torque of 14 Nm
3)
Observe acting direction of DIL switches
4)
AWG = American wire gauge
5)
Also with weather shield ASK39.1
6)
SA..61../MO are not suitable for outdoor applications.
7)
Up to 150 °C with horizontal mounting position
8)
The documents can be downloaded from http://siemens.com/bt/download.
9)
UL recognized component

Table of Contents