Siemens Building Technologies CM2N3204E / 1.1999
Landis & Staefa Division 13/20
Electromagnetic compatibility
Emissions to EN 50 081-1
Immunity to EN 50 082-2
conformance to
EMC directive 89/336/EWG
Low voltage directive 73/23/EWG
Product standards
Automatic electric controls
for household and similar uses EN 60 730
Miscellaneous
Reserve in the event of a power failure 48 h (typically)
Connection terminals for wires 2 x 1.5 mm
2
or
1 x 2.5 mm
2
Weight (incl. packing) 1.17 kg
G M B1 B2 B4 B9 Z GE E1 E2 E3 E4 E5 E6 E7 E8
G0 Y10 G GY20 GY30 UP UN
AZI65.1
F91 Q14 Q24 Q34 Q44
3204G01
Q13 Q33
G Operating voltage, AC 24 V (system potential)
G0 Operating voltage (system neutral)
M Measuring neutral
B1 Measuring signal from the room or extract air temperature detector (LG-Ni1000 / DC 0...10 V)
B2 Measuring signal from the supply air temperature detector (LG-Ni1000 / DC 0...10 V)
B4 Measuring signal from the outside detector (LG-Ni1000 / DC 0...10 V)
B9 Measuring signal from the frost detector (LG-Ni1000 / DC 0...10 V)
Z Measuring signal from peripheral devices (LG-Ni1000 / DC 0...10 V)
Y10 Control signal output for heating (DC 0...10 V)
Y20 Control signal output for cooling 1
)
(DC 0...10 V)
Y30 Control signal output for heat recovery (DC 0...10 V)
GE Signal voltage neutral for digital inputs E1 through E8
E1 Digital status input «Fire/smoke»
E2 Digital status input «Air flow signal»
E3 Digital status input «Overload hot water circulator or overtemperature electric heater battery»
E4 Digital status input «Overload of chiller or chilled water circulator»
E5 Digital status input «Overload fan»
E6 Digital status input, not used
E7 Digital input «Control input 1»
E8 Digital input «Closed input 2»
F91 Common fault status output (AC 24 V) with priority «A» and «b» or «A» or «b» (can be coded for
this output)
Q13/Q14 Potential-free relay contact output, to switch circulator or electric heater battery
Q13/Q24 Potential-free relay contact output for compressor, dx-cooling or chilled water circulator
1)
Q33/Q34 Potential-free relay contact output, to switch fan speed I
Q33/Q44 Potential-free relay contact output, to switch fan speed II
UP, UN Connections (2...3) for communication
Note: LG-Ni1000 detectors = L&S standard
Control signal outputs Y20 and Q13/Q24 are available at the same time
Connection diagram