In order to maintain synchronism within a substation, the relay can be synchronised to the nearest second or
minute using the communications interface, or a binary input.
The default date is set at 01/01/2000 deliberately to indicate the date has not yet been set. When editing the
Time, only the hours and minutes can be edited. When the user presses ENTER after editing the seconds are
zeroed and the clock begins running.
6.7.1 Time Synchronisation – Data Communication Interface
Where the data comms channel(s) is connected the relay can be directly time synchronised using the global time
synchronisation. This can be from a dedicated substation automation system or from ‘Reydisp Evolution’
communications support software.
6.7.2 Time Synchronisation – Binary Input
A binary input can be mapped Clock Sync from BI. The seconds or minutes will be rounded up or
down to the nearest vale when the BI is energised. This input is leading edge triggered.
6.8 Settings Groups
The relay provides four groups of settings – Group number (Gn) 1 to 4. At any one time only one
group of settings can be ‘active’ – SYSTEM CONFIG>Active Group setting. An output is provided to
indicate which setting group is active.
It is possible to edit one group while the relay operates in accordance with settings from another ‘active’ group
using the View/Edit Group setting.
Some settings are independent of the active group setting i.e. they apply to all settings groups. This is indicated
on the top line of the relay LCD – where only the Active Group No. is identified. Where settings are group
dependent this is indicated on the top line of the LCD by both the Active Group No. and the View Group No.
being displayed.
A change of settings group can be achieved either locally at the relay fascia, remotely over the data comms
channel(s) or via a binary input. When using a binary input an alternative settings group is selected only whilst the
input is energised (Select Grp Mode: Level triggered) or latches into the selected group after energisation of the
input (Select Grp Mode: Edge triggered).
Settings are stored in non-volatile memory.
6.9 Password Feature
The relay incorporates two levels of password protection – one for settings, the other for control functions.
The programmable password feature enables the user to enter a 4 character alpha numeric code to secure
access to the relay functions. The relay is supplied with the passwords set to NONE, i.e. the password feature is
disabled. The password must be entered twice as a security measure against accidental changes. Once a
password has been entered then it will be required thereafter to change settings or initiate control commands.
Passwords can be de-activated by using the password to gain access and by entering the password NONE.
Again this must be entered twice to de-activate the security system.
As soon as the user attempts to change a setting or initiate control the password is requested before any changes
are allowed. Once the password has been validated, the user is ‘logged on’ and any further changes can be
made without re-entering the password. If no more changes are made within 1 hour then the user will
automatically be ‘logged off’, re-enabling the password feature.
The Settings Password prevents unauthorised changes to settings from the front fascia or over the data comms
channel(s). The Control Password prevents unauthorised operation of controls in the relay Control Menu from the
front fascia.
The password validation screen also displays a numerical code. If the password is lost or forgotten, this code
should be communicated to Siemens Protection Devices Ltd. and the password can be retrieved.