Commissioning / service
NOTICE
When using a 4G dongle
Reboot the device after a 4G dongle has been connected.
For details see 4G Dongle Setup (A6V12059208).
Technical data
Power supply
Operating voltage 24 V AC (24 V, , )
AC 24 V -15 / +20 % (SELV / PELV) or
AC 24 V Class 2 (US)
48…63 Hz
Operating voltage 24 V DC
DC 24 V -15 / +20 % (SELV / PELV) or
DC 24 V Class 2 (US)
Functional ground (US)
Functional earth
The terminal for the functional ground must be
connected on the installation side with the building
grounding system (PE).
Screw terminals for wire cross sections up to
Max. 2.5 mm
2
(14 AWG)
Internal fusing
2.5 A irreversible / non-replaceable
External supply line fusing (EU)
Non-renewable fuse max. 10 A slow
or
circuit breaker max. 13 A
Tripping characteristic B, C, D per EN 60898
or
Power supply with current limitation of max. 10 A
Power consumption (for transformer planning)
Power consumption AC
16 VA
Power consumption DC
8 W
Function data
Hardware information
Processor
NXP i.MX8 DualX
Storage
2 GB RAM
8 GB eMMC
Data backup in the event of power failure
Super cap to support real-time clock (7 days).