9 | P u s l a p i s
SIEMENS CLIMATIX
3 Communications
Possible communications:
Modbus RTU by default: Baud rate 19200 , Parity EVEN, Stop bits 1, Word length 8 bit.
Modbus TCP/IP port: 502.
Modbus list parameters:
Parameters
Address
Read/Write
Gain
Mode
Main switch Off/On
H2
Display/Comm. Off/On
H4
Setpoint
H8
Dif
H10
Fan
DryCooler temp.IN value
H100
0.1
DryCooler temp.OUT value
H102
0.1
DryCooler temp.OUT alarm
H104
Fan overload
H106
Fan output 0-100%
H108
Fan work hours
H118
Pump
Supply pump (Single) Status
H200
Supply pump 1 (Twin) Status
H202
Supply pump 2 (Twin) Status
H204
Supply pump (Single) / Supply pump 1 (Twin) overload
H206
Supply pump 2 (Twin) overload
H208
Flow det. status (single pump)
H210
Flow det. alarm (single pump)
H212
Supply pump (Single) Work hours
H214
Supply pump 1 (Twin) Work hours
H216
Supply pump 2 (Twin) Work hours
H218
Adiabatic pump Status
H220
Adiabatic pump work hours
H222
Adiabatic pump overload
H224
Flow det. status adiabatic pump
H226
Flow det. alarm adiabatic pump
H228
Valve
Valve output 0-100
H300
Valve drain status
H302
Valve supply status
H304
Common
Alarm output
H400
Outside temp.
H402
0.1