Technical data of CPU 31xC 
  6.4 CPU 313C-2 PtP and CPU 313C-2 DP 
CPU 31xC and CPU 31x, Technical Data 
Manual, 01/2006 Edition, A5E00105475-06 
6-17 
Technical data 
  CPU 313C-2 PtP  CPU 313C-2 DP 
Block status  Yes 
Single-step  Yes 
Breakpoints  2 
Diagnostic buffer  Yes 
•  Number of entries (not configurable) 
Max. 100 
Communication functions  CPU 313C-2 PtP  CPU 313C-2 DP 
PG/OP communication  Yes 
Global data communication  Yes 
•  Number of GD circuits 
4 
•  Number of GD packets 
–  Sender 
–  Receiver 
Max. 4 
Max. 4 
Max. 4 
•  Size of GD packets 
–  Consistent data 
Max. 22 bytes 
22 bytes 
S7 basic communication  Yes (server) 
•  User data per job 
–  Consistent data 
Max. 76 bytes 
76 bytes (for X_SEND or X_RCV) 
64 bytes (for X_PUT or X_GET as the server) 
S7 communication   
•  As server 
Yes 
•  As client 
Yes (via CP and loadable FBs) 
•  User data per job 
–  Consistent data 
Max. 180 bytes (with PUT/GET) 
64 bytes 
S5compatible communication  Yes (via CP and loadable FCs) 
Number of connections  Max. 8 
Can be used for   
•  PG communication 
–  Reserved (default) 
–  Configurable 
Max. 7 
1 
From 1 to 7 
•  OP communication 
–  Reserved (default) 
–  Configurable 
Max. 7 
1 
From 1 to 7 
•  S7-based communication 
–  Reserved (default) 
–  Configurable 
Max. 4 
4 
From 0 to 4 
Routing  No  Max. 4 
interfaces  CPU 313C-2 PtP  CPU 313C-2 DP 
1st interface 
Type of interface  Integrated RS485 interface 
Physics  RS 485 
electrically isolated  No 
Interface power supply (15 to 30 VDC)  Max. 200 mA