Communication   
3.3 S7 connections 
  CPU 31xC and CPU 31x, Technical Data 
3-32  Manual, 01/2006 Edition, A5E00105475-06 
3.3.4  Connection resources for routing 
Number of connection resources for routing 
The CPUs with DP interface provide a different number of connection resources for the 
routing function: 
Table 3-12  Number of routing connection resources (for DP/PN CPUs) 
CPU  As of firmware version  Number of connections for routing 
31xC, CPU 31x  2.0.0  Max. 4 
317-2 DP  2.1.0  Max. 8 
31x-2 PN/DP  2.2.0  Interface X1 configured as: 
•  MPI:Max. 10 
•  DP master: Max. 24 
•  DP slave (active): Max. 14 
 
Interface X2 configured as: 
•  PROFINET: Max. 24 
319-3 PN/DP  2.4.0  Interface X1 configured as: 
•  MPI: Max. 10 
•  DP master: Max. 24 
•  DP slave (active): Max. 14 
 
Interface X2 configured as: 
•  DP master: Max. 24 
•  DP slave (active): Max. 14 
 
Interface X3 configured as: 
PROFINET: Max. 48 
Example of a CPU 314C-2 DP 
The CPU 314C-2 DP provides 12 connection resources (refer to Table 3-11): 
•  Reserve two connection resources for PG communication. 
•  Reserve three connection resources for OP communication. 
•  Reserve one connection resource for S7-based communication. 
This leaves six connection resources available for other communication service, e.g. S7 
communication, OP communication, etc. 