Communication 
  3.2 Communication services 
CPU 31xC and CPU 31x, Technical Data 
Manual, 01/2006 Edition, A5E00105475-06 
3-23 
Compatibility of the New System Status Lists  
For PROFINET IO, the system status lists had to be revamped to some extent because, 
among other things, larger configurations are now possible with PROFINET.  
You should also use these new system status lists with PROFIBUS. 
You can continue to use a known PROFIBUS system status list that is also supported by 
PROFINET. If you use a system status list in PROFINET that PROFINET does not support, 
an error code is returned in RET_VAL (8083: Index wrong or not permitted). 
Comparison of the System Status Lists of PROFINET IO and PROFIBUS DP 
Table 3-9  Comparison of the System Status Lists of PROFINET IO and PROFIBUS DP 
SSL-ID  PROFINET IO  PROFIBUS DP  Applicability 
W#16#0591  yes 
(parameter adr1 changed) 
Yes   Module status information for the interfaces of a 
module 
W#16#0A91  Yes 
(parameter adr1 changed) 
Yes   Status information of all subsystems and master 
systems (S7-300 without CPU 318-2 DP) 
W#16#0C91  Yes 
(parameter adr1/adr2 and  
set/actual type identifier 
changed) 
Yes   Module status information of a module in a central 
configuration or attached to an integrated DP or PN 
interface module using the logical address of the 
module. 
W#16#4C91  Yes 
(parameter adr1 changed) 
Yes   Not with S7-300 
Module status information of a module attached to an 
external DP or PN interface module using the start 
address 
W#16#0D91  Yes 
(parameter adr1 changed) 
Yes   Module status information of all modules in the 
specified rack/station 
W#16#0696  Yes  No  Module status information of all submodules of a 
module using the logical address of the module, not 
possible for submodule 0 (= module) 
W#16#0C96  Yes  Yes   Module status information of a submodule using the 
logical address of this submodule 
W#16#xy92  No 
(replacement: SSL-ID 
W#16#0x94) 
Yes  Rack/stations status information 
Replace this system status list with the system status 
list with ID W#16#xy94 in PROFIBUS DP, as well. 
W#16#0x94  Yes  Yes   Rack/station status information 
Detailed Information 
For detailed descriptions of the individual system status lists, refer to the manual 
System 
Software for S7-300/400 System and Standard Functions
.