S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
A5E00105492-03
5-7
$UUDQJLQJ0RGXOHVRQD6LQJOH5DFN
$UH\RXXVLQJRQHRUPRUHUDFNV"
The number of racks you need will depend on your application.
5HDVRQVIRUXVLQJDVLQJOHUDFN
• Compact, space-saving use of all your modules
• Centralized use of your modules
• Fewer signals to be processed
5HDVRQVIRUGLVWULEXWLQJPRGXOHVEHWZHHQVHYHUDOUDFNV
• More signals to be processed
• Insufficient slots available
7LS:
If you opt for installation on a single rack, insert a dummy module to the right of the
CPU (order no.: 6ES7 370-0AA01-0AA0). This gives you the option of inserting a
second rack for your application in the future, simply by replacing the dummy
module with an interface module and without having to reinstall and rewire the first
rack.
5XOHV$UUDQJLQJPRGXOHVRQDVLQJOHUDFN
The following rules apply to single-rack module installations:
• No more than eight modules (SM, FM, CP) may be installed to the right of the
CPU.
• All modules mounted on a rack must not consume more than a total of 1.2 A
from the S7-300 backplane bus.
7KHSRZHUFRQVXPSWLRQRIPRGXOHV
is listed under the technical data, e.g. 60RGXOH'DWD5HIHUHQFH0DQXDOor in
the 5HIHUHQFH0DQXDOfor your CPU