Table 5-3 Specification of fiber-optic cables for outdoor applications
Cabling Components required Specification
A cable junction is required be‐
tween the indoor and outdoor
area
Installation cables
for
outdoor applications
Installation cables for outdoor applica‐
tions:
1 cable with 4 cores per fault-tolerant
system
Both interfaces in one cable
1 or 2 cables with several shared
cores
Separate installation of the interfaces
in order to increase availability (reduc‐
tion of common cause factor)
Connector type ST or SC, for exam‐
ple, to match other components; see
below
Further specifications you may need to
observe for your plant:
UL approval
Halogen-free materials
Further specifications that may apply due
to the local conditions:
Protection against increased mechan‐
ical stress
Protection against rodents
Water-proofing
Suitable for direct underground instal‐
lation
Suitable for the given temperature
ranges
Avoid splicing cables in the field. Use pre‐
fabricated cables with pulling protection/
aids in whiplash design, including meas‐
uring log.
if necessary, instal‐
lation cables also for
the interior area
1 cable with 4 cores per fault-tolerant
system
Both interfaces in one cable
1 or 2 cables with several shared
cores