Introduction
1.2 Introduction
Compact Switch Module CSM 1277
Operating Instructions, V. 1.20, A2B00079397B
7
1.2 Introduction
What is possible?
The CSM 1277 device allows the cost-effective installation of Industrial Ethernet bus or star
structures with switching functionality.
Note
It is not possi
ble to use the CSM 1277 switch in a redundant ring because it does not support
redundancy.
Note
If the CSM 1277 switch i
s supplied over long 24 V power supply lines or networks, measures
are necessary to prevent interference by strong electromagnetic pulses on the supply lines.
These can result, for example, due to lightning or switching of large inductive loads.
One of the tests used to attest the immunity of the switch to electromagnetic interference
was the "surge immunity test" according to EN61000-4-5. This test requires overvoltage
protection for the power supply lines. A suitable device is, for example, the Dehn Blitzductor
VT AD 24 V type no. 918 402 or comparable protective element.
Manufacturer:
DEHN+SÖHNE GmbH+Co.KG Hans Dehn Str.1 Postfach 1640 D-92306 Neumarkt,
Germany
WARNING
When used under hazardous conditions (zone 2), the CSM 1277 switch must be installed in
an enclosure.
To comply with ATEX 95 (EN 60079-15), this enclosure must be at least IP54 in
compliance with EN 60529.
WARNING – EXPLOSION HAZARD: DO NOT DISCONNECT EQUIPMENT WHEN A
FLAMMABLE OR COMBUSTIBLE ATMOSPHERE IS PRESENT.