Building Technologies PXC...-U – Automation stations modular model CA1N9221en
Building Automation 23.09.2005
Concerned LED Color Status Function
Automation station RUN Green
Red
Continuously off
Continuously on
Continuously on
No supply
Supply OK, firmware OK
RESET key pressed
STATUS Red Continuously off
Continuously on
Quick flashes
Normal operation
Hardware fault detected during self-test or
automation station in "coma" operating state
No validly licensed firmware
INFO Red Freely programmable
Data traffic LON bus TX COM1 Yellow Flashing Data traffic on LON bus
COM2 Yellow Inactive
SERVICE
COM1
Red Continuously off
Flashing
Flashing acc. to wink
command pattern *)
Continuously on
LON node is configured
LON node is not configured
Physical identification of automation station
after receiving wink command
LON chip defect or service key was pressed
again
COM2 Red Inactive
Data traffic Ethernet / IP TX COM1 Yellow Inactive
(PXA30-N..., PXA30-W...)
COM2 Yellow Flashing Sends Ethernet data
SERVICE
COM1
Red
Inactive
COM2 Red Continuously off
Flashing slowly
Continuously on
Ethernet OK
IP address not configured
No link pulse
*) Wink command rhythm pattern:
2s
1s
21s
5 Hz 5 Hz
00408
2s
1s
Mounting instructions
The modular automation stations are particularly suitable for control panel front
mounting as well as flush-panel and wall mounting.
For control panel front mounting the device socket is held in place by clamps at all four
corners (no tools required for mounting). The upper housing is fixed to the device
socket with two screws.
For flush panel mounting the plug-in terminal blocks can be repositioned whilst at the
same time reversing the support bars to enable front access. The support bars absorb
the screw force and also provide the means of fixing the device to the wall.
Instead of the front cover a PXM... operator unit can be fitted on the modular auto-
mation station.
For PXM20-E mounting (ethernet cable) see the mounting instructions delivered with
the operator unit!
Insert
the PXA30… extension module fully into its socket (to a depth of 1.5 mm),
using slight force.
Then check that the plug is safely snapped on to ensure safe
and smooth functioning.
Do not touch the connector pins (electrostatic discharge)
Note
STOP
Note!
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.