Siemens RXZ95.1/LON – Gateway EnOcean/LonWorks CM2N1661en_02
Building Technologies Workflow with RXT10 and LNS plug-in 23 Sep 2011
Step Procedure
5c
Configure the gateway:
select tab Sensor 1...9:
Function not available with the RXT10.
Device: For room units QAX95.1, QAX96.1, select
setting 7
SensorID: For offline engineering, the EnOcean ID of
the room unit can be entered here, if desired.
Normally, it is learned-in online (with
connection to the network, see step 10).
SCPTmaxSendTime: Heartbeat room unit
Recommendation: Same as RXC Default
2700 [s] (45 min)
Note relating to SCPTmaxSendTime:
With the default setting of 0.0 s (OFF) and in the event the RF link
breaks down (faults, no light, etc.), the temperature value in the RXC
will change to ”invalid” when the heartbeat has elapsed. When using a
setting greater than 0.0 s, the temperature value received last will be
transmitted.
6
> Apply
(Question ”...transmit to device?“: Answer with YES)
Network > Disconnect (Attached offnet)
7
Make RXT10 bindings:
Datapoint Gateway RXC
Room Temperature: nvoHVACTemp_x nviSpaceTemp
Setpoint Offnet: nvoSetpoint_x nviSetpointOffset
8
Network > Connect (online)
9
Assign devices and install