EasyManua.ls Logo

Siemens Desigo RXC20.1 - RXC21 Connection Terminals

Siemens Desigo RXC20.1
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11/16
Siemens RXC20, RXC21, RXC22 – Room controllers CA2N3834en_09
Building Technologies 2013-06-16
Connection terminals
12345678910111213141516 1718
M
D1
GND
D2
Y1
G
Y2
G
CP–
CP+
CLA
CLB
B1
CLA
CLB
1234
QAX...
T
M
25 26 27 28
Q13
Q14
AC 230 V
Y3
G
Y4
M
Q24
Q34
5(4) A
19 19 21
N
L
N
21
L
3804A03
LonWorks®
Bus
Measured value input
B1 1 Measured value input with LG-Ni 1000 sensor
M 2 Measured value input ground
Signal inputs
D1 3 Signal input
GND 4 Signal ground
D2 5 Signal input
Triac outputs
Y1 6 AC 24 V, 0.5 A switching output
G 7 AC 24 V actuator supply
Y2 8 AC 24 V, 0.5 A switching output
G 9 AC 24 V actuator supply
Y3 10 AC 24 V, 0.5 A switching output
G 11 AC 24 V actuator supply
Y4 12 AC 24 V, 0.5 A switching output
Room unit
CP– 13 PPS2 ground
CP+ 14 PPS2 data
CLA 15 Data A
CLB 16 Data B
L
ONWORKS® bus (plug-in)
CLA 17 Data A
CLB 18 Data B
Power supply
N 19 Neutral conductor
L 21 Phase line AC 230 V +/- 10 %
Relay outputs
Q13 25 Feed for Q14, Q24 and Q34
Q14 26 N/O contact AC max. 250 V, 5 (4) A (stage 1)
Q24 27 N/O contact AC max. 250 V, 5 (4) A (stage 2)
Q34 28 N/O contact AC max. 250 V, 5 (4) A (stage 3)
Observe the technical data for the relay outputs: Max. AC 250 V, 5 (4) A
Local installation regulations must be observed.
Standard RJ45 tool socket for L
ONWORKS® devices.
1
3206Z01
2345678
1 LONWORKS®, Data A (CLA)
2 L
ONWORKS®, Data B (CLB)
3 Unoccupied
4 Unoccupied
5 Unoccupied
6 unoccupied
7 PPS2 (CP+)
8 PPS2 (CP–)
RXC21
STOP
Note!
Tool socket

Related product manuals