5
WL Circuit Breaker selection and application guide
Low Voltage Circuit Breaker
Electronic trip units
Electronic trip units (ETUs)
Power system protection is necessary to treat common types of 
abnormal occurrences, such as overloads or faults that can lead 
to electrical power system failure.
The methods for detecting and clearing such abnormalities 
and restore to normal operation is an engineered technique. 
Adequate protection requires constant measurements of certain 
system quantities, such as voltages and currents, comparing 
those system quantities, or some combination of the quantities, 
to a threshold setting computed by a systems engineer and 
set into an electronic trip unit like those available on the WL 
breakers. It’s equally important for power system protection 
to perform under normal operating conditions. If the above 
thresholds are set too low the power may be interrupted 
unnecessarily causing loss of productivity or safety provisions.
The WL circuit breaker offers a practical means of setting 
power system protection through vast selectivity available in 
its Electronic Trip Unit (ETU). WL ETUs have a wide range of 
protective settings for implementing simple or complex 
coordination schemes and configuring reliable system protection.
ETU enhanced features
• Extended Instantaneous Protection (EIP): Provides full 
  withstand capability and coordination up to the short-time   
  withstand rating regardless of the Instantaneous functional  
  setting. Without this feature de-rating of breakers could 
  reduce your system interrupt capacity by 20% or require
  higher interrupt rated breakers. 
• Dynamic Arc-Flash Sentry: Provides selective current reduction  
  settings to limit the amount of available energy downstream  
  from the WL breaker.
• Selectable I
4
t: ETU745 and 776 make it possible to 
  switchover from an I
2
t to an I
4
t inverse-time function for 
  overload protection. This selectivity increases optimization 
  of coordinated overload protection when overload fuse 
  protection is also required.
ETU basic functions
Long-time trip
The long-time delay adjustment is used to set the tripping delay 
of the circuit breaker based on the magnitude of the overcurrent 
condition (6 times l
r
). For example if the rating plug is 2000 
amps and the long-time delay is set to 10 seconds, a fault current 
of 12,000 amps (6 x 2000) will cause the breaker to trip after 
10 seconds. Long-time is an inverse of  I
2
t ramp function. This 
means the higher the current, the shorter the time the circuit 
breaker will remain closed. An Alarm LED indicator will flash 
during the delay period and a separate “Trip L” indicator will turn 
on if the breaker trips on long-time function.
Short-time trip
The short-time pickup adjustment is used to set the level of 
high current the breaker will carry for a short period of time 
without tripping. This adjustment is set in multiples of the 
value of the rating plug (Ir). Together with the short-time delay, 
this adjustment allows downstream breakers time to clear short 
circuit faults without tripping upstream breakers. Short-time 
delay is used to set the time interval the breaker will wait before 
responding to the current value selected by short-time pickup. 
There are two modes of operation: fixed and I
2
t. The  I
2
t delay 
has the characteristic of being inversely proportional to the 
square of the magnitude of the current. This means higher 
overcurrent conditions have shorter delays. An Alarm LED 
indicator will flash during the delay period and a separate 
“Trip S” indicator will turn on if the breaker trips on short-
time function.
Instantaneous trip
The instantaneous pickup adjustment is used to set the current 
level at which the breaker will trip without an intentional time 
delay. Non-delayed tripping as a result of severe overcurrent 
minimizes potential damage to the electrical system and 
equipment. This adjustment is set in multiples of I
r
.
An instantaneous override (OFF) function is available. It is 
normally set at the short-time rating of the respective breaker 
frame size. This allows the breaker to ride through high fault 
currents up to the breakers short-time withstand capability, 
however, it is self protecting above the short-time withstand 
value. An Alarm LED indicator will flash during the delay period 
and a separate “Trip I” indicator will turn on if the breaker trips 
on instantaneous function.
Ground fault
The ground fault pickup adjustment is used to set the level of 
ground current at which circuit interruption will be initiated. 
Together with ground fault delay, this adjustment allows 
selective tripping between main and feeder or downstream 
breakers. 
The ground fault delay adjustment is used to set the time interval 
(in seconds) the breaker will wait before responding once the 
ground fault pickup level has been reached. The available ground 
fault delay settings available are: inverse time (I
2
t) and/or fixed 
delay. An optional alarm LED indicator will flash during the delay 
period and a separate “Trip G” indicator will turn on if the breaker 
trips on ground fault function.