Installation
4
'Smoke 4…20 mA' analog output
Dust value
4…20 mA analog output
No dust 4 mA
Low dust value 8 mA
Medium dust value 12 mA
High dust value 16 mA
Very high dust value 20 mA
Fine dust value
4…20 mA analog output
0 μg/m³ 4 mA
30 μg/m³ 8 mA
60 μg/m³ 12 mA
90 μg/m³ 16 mA
150 μg/m³ 20 mA
Properties
With electrically isolated, passive two-wire 4…20 mA analog output.
The connection is independent of polarity.
The increment corresponds to the increment of the smoke indicator (bar graph
indicator).
The error indicator can be suppressed with the 'FXS2051 ASD Configuration
Tool' software.
'Current loop' output.