EasyManuals Logo

Siemens FDOOT241-A9-Ex User Manual

Siemens FDOOT241-A9-Ex
26 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #15 background imageLoading...
Page #15 background image
Undertaking modernization
4
Step 1: Detector modernization
4 Undertaking modernization
4.1 Step 1: Detector modernization
The following steps must be taken during each modernization:
1. For information about installing new detector bases FDB20x or FDB22x, see
chapter 'Base replacement [➙ 16]'
2. For information about configuring the detectors, see chapter 'Configuration of
detector type [➙ 17]'
3. For information about carrying out function tests for detectors, see chapter
'Test the detectors [➙ 18]'
WARNING
Work carried out by personnel who are not sufficiently qualified
Risk of explosion
Work in potentially explosive areas may only be carried out by qualified
specialists or by specially instructed persons, in accordance with the national
and international directives and regulations.
Point detectors that can only be operated in collective mode are replaced with
multiple protocol detectors. The detector lines are still operated in collective mode.
DC1192 SB3
DT1101A-
Ex
DO1101A-
Ex
SB3
DT1102A-
Ex
DC1192
Collective Ex-line
Collective Ex-line
EOL22
(Ex)
EOL22
(Ex)
Non-Ex Area Ex Area
FDOOT241-A9-Ex/
OOH740-A9-Ex
FDOOT241-A9-Ex/
OOH740-A9-Ex
FDOOT241-A9-Ex/
OOH740-A9-Ex
15
Building Technologies
A6V10443621_a_en_--
Fire Safety 2014-09-01

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FDOOT241-A9-Ex and is the answer not in the manual?

Siemens FDOOT241-A9-Ex Specifications

General IconGeneral
BrandSiemens
ModelFDOOT241-A9-Ex
CategorySecurity Sensors
LanguageEnglish

Related product manuals