4
Undertaking modernization
Step 1: Detector modernization
4.1.1 Base replacement
On collective Ex detector lines, when replacing the point detector with a multiple
protocol detector, the switch can be made to a Sinteso detector base.
Use the following detector bases:
FDB201
FDB202
FDB221
FDB222
WARNING
Using incorrect detector bases in the area at risk of explosion
Risk of explosion
When modernizing the collective Ex detector line, point detectors
FDOOT241-A9-Ex and OOH740-A9-Ex may only be used with detector bases
FDB20x or FDB22x. Do not use detector bases from the AlgoRex product
range or base adapters.
You will find information about installing the detector bases FDB20x and FDB22x in
document A6V10208546. See chapter 'Applicable documents [➙ 8]'.
16
Building Technologies A6V10443621_a_en_--
Fire Safety 2014-09-01