Loading...
Specifications
30
Building Technologies 007025_i_en_--
Fire Safety & Security Products 07.05.2010
9 Specifications
9.1 Technical data
Operating voltage 12 … 33 VDC Detector line
Operating current:
Quiescent condition
Sound activated
150 μA
1.2 mA
Maximum current connection factor 5
Quiescent current connection factor 0,5
Address connection factor 0
Separator connector factor 0
Protocol FDnet
Compatibility See 'List of compatibility'
Number of external alarm indicators that
can be connected
1 External alarm indicators
Specifications See document 007004
Number of sounds 11 Base sounder
Activation levels 2
Sound level Depending on the set tone; see chapter
'Configuration' for details
Communication protocol EAI link, only with detectors and sounder bases
with product version ≥30 and with automatic
detection
Detector line and external alarm
indicator:
Design
Spring clips
Connections
Cable cross section 0.2 … 1.5 mm²
Operating temperature -25 … +70 °C Ambient conditions
Storage temperature -30 … +75 °C
Air humidity ≤95 % rel.
Protection category according to
EN 60529/IEC 60529
IP43
Electromagnetic compatibility:
1 MHz … 1 GHz
1 GHz … 2 GHz
50 V/m
30 V/m
Dimensions (W x H x D) 153 x 27 x 93 mm Mechanical data
Housing material ABS
Colour ~RAL 9010 pure white