Network module (SAFEDLINK) FN2001
1
Indicators
9
Siemens Industry, Inc. A6V10315042_f_en_--
Building Technologies Division 2015-04-16
1.6 Indicators
LED Color Function Condition Meaning
RUN (H1) Green
Condition of the
network module
(SAFEDLINK)
Off Network module (SAFEDLINK) is defective
On Normal condition (H2 and H3 are off)
Flashes
Normal condition for degraded mode module (H2 and H3
are off)
2 (H2) Yellow Status of circuit 2
(A2, B2)
Off Normal condition
(communication on circuit 2 is OK)
On Error on circuit 2
(no communication on circuit 2)
1 (H3) Yellow Status of circuit 1
(A1, B1)
Off Normal condition
(communication on circuit 1 is OK)
On Error on circuit 1
(no communication on circuit 1)