Function (cont´d) 
  Burner operation with or without postpurge 
  Fan motors with a current draw of up to 4 A can be connected directly  starting 
current max. 20 A (for max. 20 ms) 
  Separate control outputs for 
– preignition from start command 
– postignition until shortly before the burner startup sequence is completed 
– short preignition with postignition up to the end of «TSA» 
  Separate control outputs for the actuator’s positioning directions «OPEN», 
«CLOSE» and «MIN» 
  Checked air damper operation to ensure prepurging with the nominal air volume 
 Checked positions: 
- «CLOSED» or «MIN» on startup  low-fire position 
- «OPEN» at the beginning of prepurging 
- «MIN» on completion of prepurging 
If the actuator does not drive the air damper to the required position, the burner 
startup sequence will be stopped 
  2 control outputs for the release of the second and third output stage or for load 
control 
  When load control is enabled, the control outputs for the actuator will be 
galvanically separated from the burner control’s control section 
 Connection facilities for 
– remote lockout warning device 
– remote reset 
– remote emergency shutdown 
  In addition, with LAL2 / LAL3: 
– possibility of air pressure supervision with functional test of the air pressure 
   monitor on startup 
– possibility of semiautomatic burner startup 
 
  Flame detector and flame simulation test are made automatically during burner off 
times and the prepurge time «t1» 
  If loss of flame occurs during operation, the burner control will initiate lockout 
  If automatic repetition of the startup sequence is required, the clearly marked wire 
link on the plug-in section of the LAL must be cut away  start repetition 
 
  Burner control is not in the lockout position 
  Sequence switch is in its start position 
 with LAL1, voltage is present at terminals 4 and 11 
 with LAL2 / LAL3, voltage is present at terminals 11 and 12 
  Air damper is closed 
  End switch «z» for the «CLOSED» position must feed power from terminal 11 to 
terminal 8  
  Contact of the limit thermostat or pressure switch «W» and the contacts of any 
other switching devices in the control loop between terminals 4 and 5 must be 
closed  e.g. a control contact for the oil preheaters temperature 
 
Normally closed contact of the air pressure switch must be closed  «LP» test. 
Control of the burner 
Flame supervision 
Preconditions for  
burner startup 
With the exception of LAL1