Function (cont'd) 
The following features enable the LFL1... to offer a high level of additional safety: 
-  Detector and extraneous light test are resumed immediately on completion of the 
afterburn time «t13». Fuel valves that are not closed, or not fully closed, 
immediately initiate lockout on completion of the afterburn time «t13». The test will 
only be terminated when the prepurge time «t1» of the next startup sequence has 
elapsed. 
-  The proper functioning of the flame supervision circuit is automatically checked 
during each startup phase of the burner. 
-  During the postpurge time «t6», the control contacts for the release of fuel are 
checked to ensure they have not welded. 
-  The built-in unit fuse protects the control contacts against overloads. 
 
-  Burner operation with or without postpurging 
-  Fan motors with a current draw of up to 4 A can be connected directly  starting 
current max. 20 A (max. 20 ms) 
-  Separate control outputs for one pilot valve, which will be shut on completion of the 
second safety time 
-  Separate control outputs for the actuator’s positioning directions «OPEN», 
«CLOSE» and «MIN» 
-  Checked air damper control to ensure prepurging with the nominal amount of air 
- Checked positions: 
- «CLOSED» or «MIN» on startup 
 low-fire position 
- «OPEN» at the start of prepurging 
- «MIN» on completion of prepurging 
If the actuator does not drive the air damper to the required position, the burner 
startup sequence will be stopped 
-  2 control outputs for the release of the second and third output stage, or load control 
-  When load control is enabled, the control outputs for the actuator will galvanically 
be separated from the unit’s control section 
- Connection facilities for 
- remote lockout warning device 
- remote reset 
- remote emergency shutdown 
-  With burner controls of the 01 series and direct spark flame burners, the safety time 
can be increased from 2.5 to 5 seconds by changing the circuitry (refer to 
«Connection examples»), provided the longer safety time conforms to local safety 
regulations  
 
-  With the ionization probe, in networks with earthed or nonearthed neutral 
conductor. For this kind of supervision, the flame supervision circuit is designed 
such that possible disturbances of the ionization current due to the ignition spark 
normally have no impact on the establishment of the flame signal. A short-circuit 
between ionization probe and burner ground causes loss of the flame signal 
-  With UV detector QRA2 / QRA4 / QRA10 (gas and oil burners) 
-  Simultaneous use of ionization probe and UV detector QRA2 / QRA4 / QRA10 (e.g. 
with interrupted pilot burners or gas-electrically ignited oil burners) 
 
-  If, on startup, the required input signals are not present, the burner control 
interrupts the startup sequence at the points marked by symbols and initiates 
lockout where required by safety regulations. The symbols used in this Data Sheet 
correspond to those on the burner control’s lockout indicator. 
General 
Control of the burner 
Flame supervision 
Preconditions for 
startup