13/25 
Building Technologies    CC1N7101en 
HVAC Products    27.11.2008 
Functions (cont´d) 
If lockout occurs, the outputs for the fuel valves, the burner motor and the ignition  
equipment will immediately be deactivated (< 1 second). 
 
Cause  Response 
Mains failure 
Restart 
Voltage below undervoltage threshold 
Safety shutdown 
Voltage above undervoltage threshold 
Restart 
Extraneous light during «t1»  Lockout 
Extraneous light during «tw»  Prevention of startup, lockout after 30 seconds at the latest 
 
LME41.051..., LME41.054..., LME41.092...: 
Prevention of startup 
No flame at the end of «TSA» 
LME11…, 
LME41.051...: 
Max. 3 repetitions, followed by lockout at the end of «TSA» 
 
LME2…, LME41.052..., LME41.053..., LME41.054..., 
LME41.071..., LME41.09...: 
Lockout at the end of «TSA» 
Loss of flame during operation 
LME11…, LME41.051...: 
•  Establishment of flame at the end of «TSA» → Max. 3 repeti-
tions 
•  No establishment of flame at the end of «TSA» → Lockout 
 
LME2…: 
Lockout 
 
LME41.052..., LME41.053..., LME41.054..., LME41.071..., 
LME41.09...: 
Repetition 
«LP» is welded in working position 
 
LME41...: 
None reaction
 
Prevention of startup, lockout after 65 seconds at the latest 
«LP» is welded in no-load position 
 
LME41...: 
«LP» is welded in no-load position or no connection 
(jumper) between terminal 3 and terminal 11
 
Lockout max 65 s after completion of «t10» 
No air pressure signal after completion «t10» 
 
LME41…: 
No air pressure signal after completion «t10» or 
breakdown of jumper terminal 3 / terminal 11
 
Lockout 
 
LME41...: 
Safety shutdown / restart
 
«CPI» contact is open during «tw»  Prevention of startup, lockout after 60 seconds at the latest 
 
In the event of lockout, the LME… remains locked and the red signal lamp (LED) will light 
up. The burner control can immediately be reset. This state is also maintained in the case 
of mains failure. 
 
When lockout occurs, the burner control can immediately be reset. To do this, press the 
lockout reset button for about 1 second (< 3 seconds). The LME… can only be reset 
when all contacts in the line are closed and when there is no undervoltage. 
 
If no flame is established at the end of «TSA», or if the flame is lost during operation, a 
maximum of 3 repetitions per controlled startup can be performed via «R», or else 
lockout will be initiated. Counting of repetitions is restarted each time a controlled star-
tup via «R» takes place. 
Control sequence in the 
event of fault 
Resetting the burner 
control 
Limitation of repetitions 
(only LME11…, 
LME41.051...)