9/25
Building Technologies CC1N7101en
HVAC Products 27.11.2008
Technical data
Mains voltage AC 120 V +10% / -15%
AC 230 V +10% / -15%
Mains frequency 50...60Hz ±6%
Power consumption 12VA
External primary fuse (Si) Max. 10A (slow)
Mounting position Optional
Input current at terminal 12 Max. 5A
Weight Approx. 160g
Safety class
I
Degree of protection IP40 (to be ensured through mounting)
Perm. cable length terminal 1 Max. 1m at a line capacitance of 100pF/m
(max. 3m at 15pF/m)
Perm. cable length from QRA… to
AGQ3…A27 (lay separate cable)
Max. 20m at 100pF/m
Remote reset laid separately Max. 20m at 100pF/m
Perm. cable length terminals 8 and 10 Max. 20m at 100pF/m
Perm. cable lengths other terminals Max. 3m at 100pF/m
Perm. terminal load At cosϕ 0.6 At cosϕ = 1
- Terminal 3 Max. 2.7A
(15A for max. 0.5s only LME2…)
Max. 3A
- Terminals 4, 5, 7 and 9 (11) Max. 1.7A Max. 2A
- Terminal 10 Max. 1A Max. 1A
Storage
DIN EN 60721-3-1
Climatic conditions Class 1K3
Mechanical conditions Class 1M2
Temperature range -20...+60°C
Humidity <95% r.h.
Transport
DIN EN 60 721-3-2
Climatic conditions Class 2K2
Mechanical conditions Class 2M2
Temperature range -20...+60°C
Humidity <95% r.h.
Operation
DIN EN 60 721-3-3
Climatic conditions Class 3K3
Mechanical conditions Class 3M3
Temperature range -20...+60°C
Humidity <95% r.h.
Condensation, formation of ice and ingress of water are not permitted!