15/25 
Building Technologies    CC1N7101en 
HVAC Products    27.11.2008 
Operation, indication, diagnostics (cont´d) 
After lockout, the red fault signal lamp LED will remain steady on. In that condition, 
visual diagnostics of the cause of fault according to the error code table can be acti-
vated by pressing the lockout reset button for more than 3 seconds. Pressing the reset 
button again for at least 3 seconds, interface diagnostics will be activated. Interface 
diagnostics works only if the AGK20… lockout reset button extension is not fitted. If, by 
accident, interface diagnostics has been activated, in which case the slightly red light of 
the signal lamp LED flickers, it can be deactivated by pressing again the lockout reset 
button for at least 3 seconds. The instant of switching over is indicated by a yellow light 
pulse. 
 
The following sequence activates the diagnostics of the cause of fault: 
 
EK
> 3 s
Flashing
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
Error code table
EK
> 3 s
Interface diagnostics
PC / analyzer
OCI400
EK
< 3 s
7101z04e/0305
Reset
On
Visual diagnostics
Lockout position
Lockout position Lockout position
 
 
Error code table 
Red blink code of 
signal lamp (LED) 
«AL» at 
term. 10 
Possible cause 
2 blinks  On  No establishment of flame at the end of «TSA» 
-  Faulty or soiled fuel valves 
-  Faulty or soiled flame detector 
-  Poor adjustment of burner, no fuel 
-  Faulty ignition equipment 
3 x blinks  On  «LP» faulty 
- Loss of 
air pressure signal after «t10» 
- «LP» is welded in normal position 
4 blinks  On  Extraneous light when burner startup 
5 blinks  On  Time out «LP» 
- «LP» is welded in working position 
6 blinks  On  Free 
7 blinks  On  Too many losses of flame during operation  
(limitation of repetitions) 
-  Faulty or soiled fuel valves 
-  Faulty or soiled flame detector 
-  Poor adjustment of burner 
8 x blinks  On  Free 
9 blinks  On  Free 
10 blinks  Off  Wiring error or internal error, output contacts, 
other faults 
14 blinks  On  CPI contact not closed 
 
During the time the cause of fault is diagnosed, the control outputs are deactivated 
-  Burner remains shut down 
-  External fault indication remains deactivated 
-  Fault status signal «AL» at terminal 10, according to the error code table 
 
The diagnostics of the cause of fault is quit and the burner switched on again by reset-
ting the burner control. Press the lockout reset button for about 1 second (< 3 seconds). 
Diagnostics of the cau-
se of fault