172/245 
Building Technologies Division  Basic Documentation LME7...  CC1P7105en 
Infrastructure & Cities Sector  23 Operation via AZL2…  29.11.2011 
 
List of phase display (display depending on program) 
 
 
Note: 
Display depends on program! 
 
Phase number or 
3-segment display 
and AZL2... display 
LED  Function 
Standby 
OFF  Off  Standby, waiting for heat request 
Ph08  Off  Power ON/test phase (e.g. detector test) 
Startup 
Ph21  Yellow  Safety valve ON, air pressure switch test/POC test (timeout/locking 
after 5 seconds), actuator opens in low-fire position/CLOSE position 
Ph22  Yellow  Fan motor ON or air pressure switch test/settling time 
Ph24  Yellow  Actuator travels to the prepurge position 
Ph30  Yellow  Prepurging 
Ph36  Yellow  Actuator closes until ignition load/low-fire is reached, and  
parameter 259.02: Actuator opens to a position > ignition load 
Ph38  Yellow flashing  Preignition 
Ph40  Yellow flashing  1st safety time/ignition transformer ON 
Ph42  Green  Safety time (ignition transformer OFF), flame check 
Ph44  Green  Interval: End of safety time and fuel valve 1 ON  
Interval: End of safety time and load controller release 
Interval: End of safety tiem and fuel valve 2 ON 
Ph50  Green  2nd safety time 
Ph54  Green  P259.01: Actuator opens to a position > low-fire 
Ph54  Green  P260: Actuator closes until low-fire position is reached 
oP1  Green  Interval to release of preset load controller (analog or 3-position step 
input) 
Operation 
oP  Green  Operation, modulating operation 
oP1  Green  Operation first stage 
oP2  Green  Operation second stage 
Shutdown 
Ph10  Yellow  Shutdown, actuator travels to the CLOSED position (home run) 
Ph72  Yellow  Actuator opens until high-fire position/operation shutdown is reached 
Ph74  Yellow  Postpurging 
Valve proving 
Ph80  Yellow  Test space is evacuated  
Ph81  Yellow  Checking time fuel valve 1 
Ph82  Yellow  Test space is filled 
Ph83  Yellow  Checking time fuel valve 2 
Waiting phases (start prevention) 
Ph01  Red/yellow flashing  Undervoltage 
Ph02  Yellow  Safety loop open  
Ph04  Red/green flashing  Extraneous light on burner startup (timeout/locking after 30 seconds) 
Ph90  Yellow  Pressure switch-min open  safety shutdown 
Lockout 
LOC  Red  Lockout phase