EasyManua.ls Logo

Siemens LMV51.100C2 - Page 201

Siemens LMV51.100C2
327 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
201/327
Building Technologies Basic Documentation LMV5... CC1P7550en
11 Description of connection terminals (AC 120 V) 22.05.2018
Description of connection terminals (cont’d)
Terminal
marking
Connection symbol
Safety class
Input
Output
Description of connections Electrical rating
X7-01
PIN 1
I
˜ Protective earth (PE)
PIN 2
˜ Neutral conductor (N)
PIN 3 Fuel valve 2 (oil)
AC 120 V +10 % / -15 %, 50...60 Hz,
1.6 A, (pilot duty), cosι 0.4
X7-02
PIN 1
I
˜ Protective earth (PE)
PIN 2
˜ Neutral conductor (N)
PIN 3 Fuel valve 3 (oil)
AC 120 V +10 % / -15 %, 50...60 Hz,
1.6 A, (pilot duty), cosι 0.4
X7-03
PIN 1
I
˜ Protective earth (PE)
PIN 2 ˜ Start release gas / oil CPI
AC 120 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
PIN 3 ˜ Power signal (reserve)
AC 120 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA