Representation of parameters based on the AZL5... menu structure, «OEM» level, as supplied by Siemens
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Description Value range Access
rights
Default pa-
rameter
setting
LMV51 LMV52
129/301
Siemens Building Technologies Basic Documentation LMV5... CC1P7550en
HVAC Products 7 Display and operating unit AZL5... 13.08.2004
QRI (QRB) AND ionization QRI_B & ION
SensOperPhOil QRI(QRB) or ionization with plausibility check, only 1 flame de-
tector connected
QRI (QRB) OR ionization
QRI (QRB) AND NOT ionization
QRI (QRB) – ionization input will not be evaluated
Ionization AND NOTQRI (QRB)
Ionization – QRI (QRB) input will not be evaluated
QRI (QRB) AND Ionisation
1 Sensor
QRI_B / ION
QRI_B & / ION
QRI_B
ION & / QRI_B
ION
QRI_B & ION
OEM 1 sensor x
RepetitCounter OEM x x
HeavyOil Rep. counter: Immediate start heavy oil 1..16 OEM 3 x x
StartRelease Rep. limit value: Start prevention 1..16 OEM 10 x x
SafetyLoop Rep. limit value: Safety loop 1..16 OEM 16 x x
ValveProving Settings for valve proving OEM x x
ValveProving-
Type
Type and time of proving test No VP
VP startup
VP shutdown
VP stup/shd
OEM VP shut-
down
x x
Config_PM-
VP/CPI
Configuration of input on PM-VP or CPI PS-VP
CPI Gas
CPI Gas + Oil
CPI Oil
OEM PS-VP x x
VP_EvacTme Proving test evacuation time 0.2..3 s OEM 3 s x x
VP_TmeAtmPre
ss
Proving test time atmospheric pressure MinT_VP_AtmPress..63 s OEM 10 s x x
VP_FillTme Proving test filling time 0.2..3 s OEM 3 s x x
VP_Tme_GasPr
ess
Proving test time gas pressure MinT_VP_GasPress..63 s OEM 10 s x x
ProductID Displaying the burner control's HW version User x x
ASN Type reference 1..15 characters User "LMV52.200
A2"
x x
ProductionDate Production date 01.01.00..31.12.99
01-01-00..12-31-99
User --- x x
SerialNumber Serial number 0..65535 User --- x x
ParamSet Code Preselected parameter set: Customer code 0..255 User 20 x x
ParamSet Vers Preselected parameter set: Version 0..65535 User 430 x x