Siemens Building Technologies Basic Documentation LMV5... CC1P7550en
HVAC Products 19 Addendum 4: LMV52... with O2 trim control and O2 module 13.08.2004
19.7 Auxiliary functions
19.7.1 Warning when flue gas temperature is too high
If a flue gas temperature sensor is connected and activated, a warning is delivered in
case the adjusted flue gas temperature is exceeded. Excessive flue gas temperatures
are an indicator of increased boiler losses boiler should be cleaned. The warning
threshold for gas- and oil-firing can be set separately.
Parameter: MaxTempFlueGas Gas
Parameter: MaxTempFlueGas Oil
19.7.2 Combustion efficiency
If an O
2 sensor, a combustion air and flue gas temperature sensor is connected and
activated, the combustion efficiency will be calculated and displayed.
Parameter: Combustion air temperature sensor (NoSensor, Pt1000,
LG-Ni1000)
Parameter: Flue gas temperature sensor (NoSensor, Pt1000, LG-Ni1000)
To ensure that the calculation will be made correctly, the fuel parameters must be se-
lected and set in accordance with the type of fuel burnt.
Also refer to section 19.10.2 Parameterization
The calculation is made according to the following formula (1. BimSchV = 1. Bundes-
Imissionsschutzverordnung = First Federal Imission Protection Decree):
Flue gas volume ratio:
V_atrNmin
V_afNmin
AVft =
O2 value dry:
O2_tr =
AVft O2ContentAir
O2ContentAir
O2Value_Wet
+ AVft - 1
Flue gas losses:
()
airpplysugasflueB
trOContentAirO
A2
qa
ϑϑ
+
=
_22
Efficiency:
qaF
=
%100
η