EasyManua.ls Logo

Siemens LMV51 Series - Page 287

Siemens LMV51 Series
299 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
287/301
Siemens Building Technologies Basic Documentation LMV5... CC1P7550en
HVAC Products 19 Addendum 4: LMV52... with O2 trim control and O2 module 13.08.2004
19.12 Setting notes
(Summary of the most important rules for setting O2 trim control)
19.12.1 Parameter settings
Parameterize all truly air-influencing actuators as air-influencing actuators
If changing the parameter settings, O2 trim control must be readjusted.
19.12.2 Setting O2 ratio control
Set sufficient excess O2
Set the amount of excess air of the ratio curve such that, whatever the
environmental conditions (combustion chamber and fuel pressure, tem-
perature and pressure of the combustion air), the set residual oxygen
content will lie above the O
2 setpoints required by O2 trim control.
Example:
1
2
3
4
5
6
O
2
(%)
100 %
Load (%)
Curvepoints
O
2
ratio control
O
2
setpoint
O
2
min value
Change of O
2
ratio control
due to ambient conditions
7550d31e/0903
1 2 3
4
5
Parameterized load proportional to the fuel rate
The burner load parameterized at the curvepoints must be proportional to the ac-
tual burner load. To make the setting, determine the burner load with the help of
the fuel counter.
Curvepoint 1
The first curvepoint should have an adequate distance below curvepoint d. This
means that the curve for reducing the air rate is also defined below point
d. As a
guide value, point
c should lie at about half the load of point d. Point d should
be smaller than or equal to the low-fire load.
If, in the low-fire position, no further air reduction is possible (e.g. because the air
damper has already fully closed), curvepoint 1 must be selected as the low-fire
point. In that case, O2 trim control will only be performed up to curvepoint 2.

Table of Contents

Other manuals for Siemens LMV51 Series

Related product manuals