EasyManua.ls Logo

Siemens LMV51 Series - Page 290

Siemens LMV51 Series
299 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
290/301
Siemens Building Technologies Basic Documentation LMV5... CC1P7550en
HVAC Products 19 Addendum 4: LMV52... with O2 trim control and O2 module 13.08.2004
19.13 Technical data
Refer to section 14 Technical data!
Mains voltage «X89-01» AC 230 V –15 % / +10 %
Safety class
I with parts according to II
as per DIN EN 60 730-1
Transformer AGG5.220
- Primary side
- Secondary side
AC 230 V
AC 12 V (2x)
Mains frequency 50...60 Hz ±6 %
Power consumption 4 VA
Degree of protection IP 54, housing closed
Storage
DIN EN 60 721-3-1
Climatic conditions class 1K3
Mechanical conditions class 1M2
Temperature range -20...+60 °C
Humidity < 95 % r.h.
Transport
DIN EN 60 721-3-2
Climatic conditions class 2K2
Mechanical conditions class 2M2
Temperature range -30...+70 °C
Humidity < 95 % r.h.
Operation
DIN EN 60 721-3-3
Climatic conditions class 3K5
Mechanical conditions class 3M2
Temperature range -20...+60 °C
Humidity < 95 % r.h.
Condensation, formation of ice or ingress of water are not permitted!
Basic unit LMV52...
PLL52...
Environmental conditions