Building Technologies Division LMV52… with MM440 Variable Speed Drive CC1A7550.2en
Industry Sector 2 Parameters 20.05.2011
Parameter No. Setting Description
28 Motor temp. sensor P0601 1 PTC thermistor (check motor sensor for compatibility)
29 Motor temp. reaction P0610 2 Warning, no reaction, trip F0011 (default)
30 Activate «AOP» to automatically display run screen
Upon powering up the Variable Speed Drive with AOP, perform the following:
* Simultaneously press <Fn> & <P> key to enter main menu
* Enter on «SETUP»
* Enter on «Start Hel
* Change to «OFF» and store parameter
It is NOT necessary to change the remaining MM440 default parameter settings
unless for reasons particular to the motor / fan combination or site conditions!