Hardware installation
5
NE8000 cabinets
36
Building Technologies A6V10062437_a_en
Fire Safety & Security Products 30.06.2013
WARNING
When entering the metallic frame of the cabinet, wires should be protected by a self-
extinguishing plastic cord guard (UL94-V2 flammability rating).
(Not provided in the supply).
Wiring (1) – Front view of cabinet (arrow indicates cut-out holes)
Wiring (2) – Entrance hole indicated by arrow
5.1.2.1 NK8021 modem mounting in an NE8000 cabinet
1. Screw in the modem holder brackets using the holes provided in the back of the
cabinet.
2. Slide the modem plate into the brackets.
3. Align the holes in the sides of the modem plate with the clips on the front of the
brackets and then press down on the clips to fix the modem in place.
4. Connect the serial cable to the NK82xx.
5. Connect the power supply.