4.3 Technical CO alarm
The 'Technical CO Alarm' mode can only be selected on the neural fire detector
OOHC740.
NOTICE
The system is not controlled as laid down in EN
54
-
2
Infringement of the EN 54-2 standard
The signals for CO detection or temperature recording must not be used to
control fire detection equipment in accordance with EN
54
-
2.
4.3.1 Parameter sets for the 'Technical CO Alarm'
4.3.1.1 Description
(Parameter set numbers in brackets)
Robust EU1 (0):
Default device parameter set with a static alarm threshold of 60 ppm CO. This
parameter set has a large compensation range and rapid compensation. Warning
level 3 is not output in the default device parameter set.
Balanced EU2 (1):
This parameter set corresponds to the dynamic CO alarm thresholds according to
EN 50291. The parameter set has a small compensation range.
Static 40 (4):
This parameter set has a static alarm threshold of 40 ppm CO. The parameter set
has a small compensation range.
Static 50 (5):
This parameter set has a static alarm threshold of 50 ppm CO. The parameter set
has a small compensation range.
Static 60 (6):
This parameter set has a static alarm threshold of 60 ppm CO. The parameter set
has a small compensation range.
Balanced US1 (7):
This parameter set corresponds to the dynamic CO alarm thresholds according to
UL 2034. The parameter set has a small compensation range.