Mounting / Installation
Detector base DB72x and detector base (collective) DB110
5
74 | 108
Building Technologies
A6V10305793_m_en_
--
Fire Safety
2016-02-15
5.2 Detector base DB72x and detector base (collective)
DB110
Install the detector base DB72x or DB110 directly on the ceiling.
Insert the cables into the detector base. You have the option of using the
following types of line:
Recess-mounted cable entry
Surface-mounted cable entry (cable diameter max. 8 mm)
NOTICE
Incorrect laying of cables
Damage to cables and difficulties when installing the point detector
The cable loops must be placed flat in the base bottom.
The bare length of the cables is approximately
8…10
mm.
1 Minimum Ø 40 mm 2 Maximum Ø 90 mm
Please note the limitations
when using the detector base DB721D.
See chapter 'Connection diagram, collective [ 87]'.
In the case of the detector bases DB721 and DB722, the
C
-
NET
detector line is
not interrupted even if a point detector is not used.
Only use the detector ba
se DB110 on collective detector lines.
1
2