EasyManua.ls Logo

Siemens OP110 - Cable entry

Siemens OP110
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mounting / Installation
5
Cable entry
43
Building Technologies A6V10316298_e_en_--
Fire Safety 2014-05-21
5.8 Cable entry
The detector bases DB110, DB110x and DB110xx feature four screw terminals. A
maximum of 2 cables may be connected to each screw terminal.
The cable cross section of the screw terminals is 0.2…1.6 mm
2
.
Terminal name Connection
1a +Connection for external alarm indicator
1b +Collective detector line IN and OUT
5 -Collective detector line IN (from the control panel) / -
external alarm indicator
6 -Collective detector line OUT (from the EOL) / -external alarm
indicator
NOTICE
Incorrect laying of cables
Damage to cables and difficulties when installing the point detector
The cable loops must be placed flat in the base bottom.
The bare length of the cables is approximately
8…10
mm.
5.8.1 Auxiliary terminals DBZ1190-AA/-AB
Use the following auxiliary terminals for multiple connections:
l DBZ1190-AB connection terminal 1…2.5 mm²
l DBZ1190-AA micro terminal 0.28…0.5 mm²
Detector base with connection terminals and micro terminals

Table of Contents

Related product manuals