Specifications
8
Technical data for heat detectors HI110 / HI112
55
Building Technologies A6V10316298_e_en_--
Fire Safety 2014-05-21
Ambient conditions
Operating temperature/permissible
ambient temperature:
l HI110 -10…+50 °C
l HI112 with 'A2S' parameter set -10…+50 °C
l HI112 with 'B' parameter set -10…+65 °C
Storage temperature -30…+70 °C
Air humidity ≤95 % rel.
Protection categories according to
EN 60529 / IEC 60529:
l Bases DB110, DB110x, DB110xx
(all installation types)
IP40
l Bases DB110, DB110x, DB110xx with
detector base seal RS720
IP42
l Bases DB110, DB110x, DB110xx with
base attachment wet BA721
IP44
Electromagnetic compatibility:
l 10 kHz…1.8 GHz 50 V/m
l 1.8 GHz…2.5 GHz 20 V/m
Mechanical data Color ∼RAL 9010 pure white
Standards European standards EN 54-5