EasyManua.ls Logo

Siemens OpenAir GLB141.1P

Siemens OpenAir GLB141.1P
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OpenAir GLB Enhanced Non-Spring Return Rotary Electronic Damper Actuator Technical Instructions
Document Number 155-785
January 20, 2017
Siemens Industry, Inc. Page 13
Troubleshooting
WARNING:
Do not open the actuator.
If the actuator is inoperative, replace the unit.
Start-Up/
Commissioning
24 Vac/dc
Two-position/
Floating 24 Vac/dc
GLB14x
1. Connect a Digital Multimeter (DMM) to the supply voltage wires.
2. Verify that the supply voltage is between 19.2 and 28.8 Vac/dc.
3. Turn off the power supply.
Check Operation:
1. Connect all wires per Figure 18.
2. Apply a control signal (24 Vac/dc) to wires 1 (red) and 6 (violet).
3. Allow the actuator shaft coupling to rotate from 0° to 90°.
4. Stop applying the control signal to wires 1 (red) and 6 (violet).
5. Apply a control signal (24 Vac/dc) to wires 1 (red) and 7 (orange).
6. Allow the actuator shaft coupling to rotate from 90° to 0°.
Check Auxiliary Switch A:
1. Set the DMM dial to ohms (resistance) or continuity check.
2. Connect wires S1 and S3 to the DMM. The DMM should indicate open circuit or no
resistance.
3. Apply a control signal (24 Vac/dc) to wires 1 (red) and 6 (violet). The DMM should
indicate contact closure as the actuator shaft coupling reaches the setting of Switch A.
4. Stop applying the control signal to wires 1 (red) and 6 (violet).
5. Connect wires S1 and S2 to the DMM. The DMM should indicate open circuit or no
resistance.
6. Apply a control signal (24 Vac/dc) to wires 1 (red) and 7 (orange). The DMM should
indicate contact closure as the actuator shaft coupling reaches the setting of Switch A.
Check Auxiliary Switch B:
1. Set the DMM dial to ohms (resistance) or continuity check.
2. Connect wires S4 and S6 to the DMM. The DMM should indicate open circuit or no
resistance.
3. Apply a control signal (24 Vac/dc) to wires 1 (red) and 6 (violet). The DMM should
indicate contact closure as the actuator shaft coupling reaches the setting of Switch B.
4. Stop applying the control signal to wires 1 (red) and 6 (violet).
5. Connect wires S4 and S5 to the DMM. The DMM should indicate an open circuit or no
resistance.
6. Apply a control signal to wires 1 (red) and 7 (orange). The DMM should indicate contact
closure as the actuator shaft coupling reaches the setting of Switch B.

Related product manuals