35/44
Siem ens GMA..1 actuators with spring return CM2Z4614en
Building Technologies 2018-01-11
8 Technical data
Operating voltage AC
Frequency
Operating voltage DC
GMA..1E/MO
Safety extra-low voltage (SELV) or
Protection by extra-low voltage (PELV) as per
Requirements for external safety insulating transformer (100% duty)
Supply line fuse
Power consumption: GMA1.. : Running
GMA1.. : Running
GMA12.., GMA13.. : Holding
GMA16.. : Holding
AC 24 V °20 % % or
AC 24 V class 2 (US)
50 / 60 Hz
DC 24…48 V °20 %
DC 24 V °20 %
HD 384
as per EN 61 558
max. 10 A
AC: 5 VA / 3.5 W
DC: 3.5 W (with DC 24 V)
AC/DC: 2 W
AC/DC: 2.5 W
Operating voltage
Frequency
Supply line fuse
Power consumption: Running
Holding
AC 230 V ° 10 %
50/60 Hz
max. 10 A
7 VA / 4.5 W
3.5 W
Nominal torque
Maximum torque (blocked)
Min. resetting torque (on power failure)
Min. holding torque
Nominal rotary angle (with position indication)
Maximum rotary angle (mechanic limitation)
Runtime for rotary angle 90° (motor operation)
Closing time with return spring (on power failure)
Rotary direction defined by:
Mounting type (GMA...1)
Mechanical life
7 Nm
21 Nm
7 Nm
7 Nm
90 °
95° ±
90 s
15 s
clockwise/counterclockwise
10
5
cycles
Operating voltage AC 24 V/DC 24…48 V (wires 1-2) Open (0° 90°)
Operating voltage AC 230 V (wires 3-4) Open (0° 90°)
Operating voltage AC 24 V/DC 24…48 V (wires 1-2)
Open: Switching current (wires: AC 1-6 / 2-6; DC 2-6)
Close: Switching current (wires: AC 1-7 / 2-7; DC 2-7)
> AC/DC 8 mA
> AC/DC 8 mA
Input voltage Y (wires 8-2)
Current consumption
Input resistance
Max. permissible input voltage
Protected against faulty wiring
Neutral zone for non-adjustable characteristic function
for adjustable characteristic function
Hysteresis for non-adjustable characteristic function
for adjustable characteristic function
DC 0...10 V / 2...10 V
0.1 mA
> 100 kς
DC 35 V
max. AC 24 V/DC 24…48 V
200 mV
2 % of ΧU
70 mV
0.7 % of ΧU
Modbus RTU
RS-485, not galvanically separated
Number of nodes Max. 32
Address range 1...247 / 255
Default: 255
Transmission formats 1-8-E-1 / 1-8-O-1 / 1-8-N-1 / 1-8-N-2
Default: 1-8-E-1
Baudrates (kBaud) Auto / 9.6 / 19.2 / 38.4 / 57.6 / 76.8 /
115.2
Default: Auto
Termination 120 Ω el. Switchable
Default: Off
Adjustable with 2 potentiometers
Offset Uo
Span ΧU
Max. permissible input voltage
Protected against faulty wiring
DC 0...5 V
DC 2...30 V
DC 35 V
max. AC 24 V/DC 24…48 V
Supply, AC 24 V/
DC 24…48 V
(SELV/PELV)
for GMA12.., GMA13..,
GMA16..
AC 230 V supply
for GMA32..1
Function data
Inputs
Positioning signal for GMA12..1
Positioning signal for GMA32..1
Positioning signal for GMA13..1
Positioning signal
for GMA16..1
Communication
Adjustable characteristic
function for GMA163.1, 164.1

Related product manuals