16
PAD-4
Installation, Operation and Maintenance Manual
2.6.7 AC Fail Relay
AC Fail Relay provides a normally closed (N.C.)
Form A contact which will be de-energized
without delay if AC is low or lost. It provides a
local signal (audible and visual) of AC fail at the
protected premises. (Refer to Figure 2-16.)
TB11 TB12 TB13
1+
1-
1
2+ 2- 2
COM
NO
NC
11
1
DO NOT USE
COM NC
PAD-4
HTRI-S
#1
HTRI-S
#2
1+
1-
2+
2-
3+
3-
4+
4-
1+
1-
2+
2-
TB12
FS-250
FS-DLC LOOP
LOOP CKT
TB13
TB3
EOL 24K
1/2W, 5%
P/N 140-034677
EOL
3.6K, 1/4W
P/N 140-830185
OR
470 OHMS, 1/4W
P/N 140-820164,
AS APPLICABLE
EOL
*
*
NOTES:
1. For U.S. Installations: Program HTRI-S #1 as Status causing,
which will not cause the DACT to signal but will cause a local
visual and audible signal. It provides a local signaling of AC fail at
the protected premises.
3. Program HTRI-S #2 as Trouble causing, which will cause the
DACT to signal for all common troubles (including AC fail with
reporting delay).
2. For Canadian Installations: Program HTRI-S #1 as Trouble
causing, which will cause the DACT to signal and will also cause a
local visual and audible signal at the protected premises. Program
the DACT to send a Primary Power Failure signal to the receiving
unit when this HTRI-S is active.
54321
54321
INPUT 1
INPUT 2
EOL
*
EOL
3.6K, 1/4W
P/N 140-830185
OR
470 OHMS, 1/4W
P/N 140-820164,
AS APPLICABLE
*
Figure 2-16
AC Fail Relay Connection Example
2.6.8 Ground Fault Relay
GND FLT Relay, located on the PAD-4-CLSA
module, provides a Normally Open (N.O.) Form
A contact which will be energized if ground fault
is detected. PAD-4-MB must be configured for
ULC operation for the contact to activate. Refer to
the PAD-4-CLSA installation instructions, P/N
315-050254 for more information.