PAD-4 Operation, Installation, and Maintenance Manual
5. PROGRAMMING
The PAD-4 functions are programmed with a 10-
position DIP switch and ten 3-position jumpers.
The following section describes each setting.
5.1 DIP SWITCH SETTINGS
The 10-position DIP switch allows you to select
the following:
How long will the unit wait before indicating a
loss of AC in UL installations. Loss of AC
settings are disabled in Canadian installations
and AC Fail will be reported immediately.
Which input (Input 1 or Input 2) will control
the NAC outputs
Which outputs to wire as Style Z (Class A)
and Style Y (Class B)
Auxiliary power output operation on AC
power fault
Which outputs to operate as steady outputs,
ANSI temporal or Carbon Monoxide (CO)
alarms.
Refer to Figure 2-5 for the location of the DIP
switch on the circuit board assembly.
All DIP switches are factory set for off; verify proper
settings for proper system operation. Slide the
switches up for OFF and down for ON.
Note: The unit checks DIP switch settings
only when reset. If you change these switch
settings, you must push S2 reset switch to
recognize the new DIP switch settings.
ON
10987654321
SEITRAPDEVLOVNIREHTODNA,NOITCIDSIRUJGNIVAHSEITIROHTUA,SRELLATSNI,SRESUOTECITON
dradnatSehtnistnemeriuqerehthtiwylpmocottcudorpehtrofredronI.erawtfoselbammargorp-dleifsetaroprocnitcudorpsihT
otdetimilebtsumsnoitporoserutaefgnimmargorpniatrec,468LU,smetsySmralAeriFrofseirosseccAdnastinUlortnoCrof
.wolebdetacidnisallatadesutonroseulavcificeps
erutaeF)N/Y(?468LUnidettimrePsgnitteSelbissoP
)4.1.5noitcesotrefeR(
468LUnidettimrepsgnitteS
gnitropeRliaFCAY
detroperebrevenlliW)1N
deyaledtoN)2
smetsyslacolrofdesU*
N
setunim06deyaleD)3Y
setunim081deyaleD)4Y